Duct Air Heater - No Control
Circular Duct Air Heaters comprising of electric resistance elements, mounted in a pregalvanised steel casing. Every heater is fitted with a high temperature safety cut out operating at 120°C complete with push button manual reset.
Available in 100, 125, 150, 200, 250, 315 and 400mm diameter sizes. The air velocity across the heater elements must be greater than 2m/s and installed a minimum distance of one metre from the exhaust outlet of the fan unit. All fans supplying heaters above 6 kW should be fitted with an off-delay timer to dissipate any residual heat when the system is shut down.
Duct heaters must be used in conjunction with a fan heater controller and a temperature thermostat (room or duct) and an air pressure/flow switch.
DIMENSIONS:
Diameter | kW | Stages | Phase | Amps | Stock Ref No |
100mm | 0.75 | 1 | 1 | 3.3 | 10531100 |
125mm | 1.0 | 1 | 1 | 4.4 | 10531125 |
150mm | 1.5 | 1 | 1 | 6.5 | 10531150 |
200mm | 2.0 | 1 | 1 | 8.7 | 10531200 |
250mm | 3.0 | 1 | 1 | 13.1 | 10531250 |
315mm | 4.5 | 1 | 1/3 | 14.6 | 10531315 |
400mm | 9.0 | 1 | 1/3 | 39.1 | 10531400 |
PDF DOWNLOADS:
Raadpleeg de tab Downloads voor technische informatie
ESTIMATED RUNNING COSTS
Calculate estimated running costs for this product using the tool below.
For average costs, leave the default values in place or enter your own figures in the boxes to recalculate.
Where a product has multi speeds, a typical installation has been used for the below calculations.
Based on the inputted figures, estimated running costs would be:
Overview
Circular Duct Air Heaters comprising of electric resistance elements, mounted in a pregalvanised steel casing. Every heater is fitted with a high temperature safety cut out operating at 120°C complete with push button manual reset.
Available in 100, 125, 150, 200, 250, 315 and 400mm diameter sizes. The air velocity across the heater elements must be greater than 2m/s and installed a minimum distance of one metre from the exhaust outlet of the fan unit. All fans supplying heaters above 6 kW should be fitted with an off-delay timer to dissipate any residual heat when the system is shut down.
Duct heaters must be used in conjunction with a fan heater controller and a temperature thermostat (room or duct) and an air pressure/flow switch.
Technical
DIMENSIONS:
Diameter | kW | Stages | Phase | Amps | Stock Ref No |
100mm | 0.75 | 1 | 1 | 3.3 | 10531100 |
125mm | 1.0 | 1 | 1 | 4.4 | 10531125 |
150mm | 1.5 | 1 | 1 | 6.5 | 10531150 |
200mm | 2.0 | 1 | 1 | 8.7 | 10531200 |
250mm | 3.0 | 1 | 1 | 13.1 | 10531250 |
315mm | 4.5 | 1 | 1/3 | 14.6 | 10531315 |
400mm | 9.0 | 1 | 1/3 | 39.1 | 10531400 |